 Temperature Controller
DIN-sized (48 x 48 mm) Temperature Controller With Digital Setting
Compact, low-cost Temperature Controller Incorporates proportional adjustment and reset adjustment function. Incorporates a plug-in socket, thus allows to DIN-track and flush mounting.
E5C4
Ordering Information
Temperature Controllers
Setting method Indication method Control mode Output Model Thermocouple (with sensor burnout detection circuit) Relay Voltage (for driving SSR) P Relay Voltage (for driving SSR) Note: E5C4-R20K E5C4-Q20K E5C4-R40K E5C4-Q40K E5C4-R20J E5C4-Q20J E5C4-R40J E5C4-Q40J Platinum resistance thermometer JPt100 E5C4-R20P E5C4-Q20P E5C4-R40P E5C4-Q40P
Digital setting
Digital indication
ON/OFF
When placing an order, specify the standard temperature range and supply voltage in addition to the model number. (e.g., E5C4-R20K 0C to 399C 100/110 VAC)
Accessories (Order Separately)
Name Front Connecting Socket Back Connecting Socket (for flush mounting) Watertight Cover P2CF-08 P3G-08 Y92A-48N Model
Temperature Ranges
Input Thermocouple K (CA) Chromel vs. alumel Range C F Setting 0 to 399 32 to 799 1C/F 0 to 999 32 to 999 1C/F J (IC) Iron vs. constantan 0 to 399 32 to 999 32 to 799 1C/F Platinum resistance thermometer JPt100 0 to 99.9 32 to 199 0.1C/1F
1
E5C4
E5C4
Specifications
Ratings
Supply voltage Operating voltage range Power consumption Input Control mode Setting method Indication method Control output 100/110, 200/220, 110/120, 220/240 VAC, 50/60 Hz 90% to 110% of rated supply voltage Approx. 2 VA Thermocouple (with sensor burnout detection circuit) or platinum resistance thermometer ON/OFF or P control Digital setting Digital indication Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA) Voltage output for SSR: 10 mA at 5 VDC (with short-circuit protection) H: 51 V; L: 0.5 V max.
Characteristics
Setting accuracy Indication accuracy Indication range Hysteresis Proportional band Proportional period Reset range (see note 1) Insulation resistance Dielectric strength Vibration resistance Shock resistance Life expectancy Ambient temperature Ambient humidity Enclosure ratings Weight Note: 2% FS max. 2% FS max. Within set temperature range Approx. 0.2% FS (fixed) 3% FS (fixed) Relay output: Voltage output: Approx. 20 s Approx. 2 s
1.5% FS min. (variable) 20 M min. (at 500 VDC) 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts Malfunction: 10 to 55 Hz, 0.3-mm double amplitude for 10 min each in X, Y, and Z directions Destruction: 16.7 Hz, 4-mm double amplitude for 2 hrs each in X, Y, and Z directions Malfunction: 147 m/s2 (15G), 3 times each in 6 directions Destruction: 294 m/s2 (30G), 3 times each in 6 directions Mechanical: 10,000,000 operations min. Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load) Operating: Operating: -10C to 55C (with no icing) 45% to 85%
Front panel: IEC standard IP40 (see note 2) Terminals: IEC standard IP00 Approx. 200 g (with flush-mounting adapter)
1. The reset adjuster of any E5C4 model with ON/OFF control is used to correct any error of the set temperature that is displayed so that the displayed temperature will coincide with the temperature that has been preset. The reset shaft of any E5C4 is used to reset the E5C4 model with proportional control. 2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48N.
2
E5C4
E5C4
Nomenclature
Temperature indicator
Operation indicator Digital switch for temperature setting RESET shaft
Negative Value Display (Example: -18C)
Overflow Display
The following will be displayed if the sensor burnout detection circuit operates or the process value exceeds the temperature range that has been preset. (Except models with a set temperature range from 0C to 399C, 32F to 799F and 32F to 199F.)
Indicates that the temperature is below 0C. Note: The E5C4 does not have a parameter display any temperature below 0C. Therefore, the accuracy of any temperature below 0 displayed by the E5C4 cannot be guaranteed.
0C to 999C or 0C to 99.9C or 32F to 999F
0C to 399C
32F to 799F
32F to 199F
Operation Indicator
Indicator Red Lit Not lit ON OFF Output
3
E5C4
E5C4
Dimensions
Note: All units are in millimeters unless otherwise indicated. Terminal Arrangement (Bottom View)
48 x 48
44.8 x 44.8
Dimensions with Flush-mounting Adapter (Accessory), and Back Connecting Socket (Sold Separately)
Panel Cutout
Flush-mounting adapter Panel Y92F-30 Flush-mounting adapter P3G-08 Back connecting socket 60 min.
60 min.
Tightening screw (96) (see note)
Note:
109 mm for US08 Back Connecting Socket
Side-by-side Mounting of N Controllers N L 2
93 +1 0
3
4
5
6
141 +1 189 +1 237 +1 285 +1 0 0 0 0
Note:
1. Recommended panel thickness is 1 to 4 mm. 2. Close side-by-side mounting is possible (in a single direction).
Accessories (Order Separately)
P2CF-08 Front Connecting Socket
Terminal Arrangement/ Internal Connections (Top View) Mounting Holes
Eight, M3.5 x 7.5 sems
Two, 4.5 dia. or Two, M4 70 max. Two, 4.5-dia. holes
Note:
50 max. 20 max.
Can also be mounted to a DIN track.
4
E5C4
P3G-08 Back Connecting Socket (for Flush Mounting)
27 dia.
E5C4
Terminal Arrangement/ Internal Connections (Bottom View)
Installation
Connections
Input
Connect a thermocouple or platinum resistance thermometer to the E5C4 as shown in the following illustration.
Voltage output (Terminal 6 is an NC terminal) Platinum resistance thermometer input Relay output
Thermocouple input
Supply voltage 100/110, 200/220, 110/120, 220/240 VAC, 50/60 Hz
Output
If the load circuit is a heating control system, be sure to connect the load to terminals 4 and 5. If the load circuit is a cooling control system, be sure to connect the load to terminals 4 and 6. If the heating control system is connected to terminals 4 and 6 or the cooling control system is connected to terminals 4 and 5, the temperature of the heating control system or cooling control system will be abnormal and a serious accident may result. If the E5C4 is in frequent operation, such as proportional operation, add an appropriate external relay to the E5C4 by considering the capacity of the load and the life of the relay. Do not ground the output of any E5C4 that has voltage output, otherwise the process temperature may not be accurate.
Power Supply
If a single power supply is used for the E5C4 and the load, the supply voltage of the power supply may vary greatly when the load is open or closed if the capacity of the power supply is not large enough. Make sure that the capacity of the power supply is large enough so that the supply voltage range will be always from 90% to 110% of the rated supply voltage. The E5C4 operates at either 50 or 60 Hz.
5
E5C4
E5C4
Precautions
Mounting
Track Mounting (E5C4 with P2CF-08) When mounting two or more E5C4 models with track-mounting sockets, leave a space of approximately 20 mm on both sides of the sockets where hooks are located.
Dismounting
If flush mounted, loosen the screw of the adapter and disengage the hooks for dismounting.
Hook Duct
P2CF-08
Panel
Flush Mounting Insert E5C4 into the square hole of the panel and insert an adapter from the back so that there will be no space between E5C4 and the panel. Then, secure the E5C4 with a screw.
Temperature Setting
The leftmost digit of any E5C4 that has a set temperature range from 0C to 399C will increase by 1 within a range of 0 to 3 each time the push button for the leftmost digit is pressed. The leftmost digit indicating 3 will change to 0 when the push button is pressed.
Others
Tightening screw
The P3G-08 can be wired in the same way as the P2CF-08.
Do not remove the housing of the E5C4, otherwise the housing may break. To clean the surface of the E5C4, use a soft cloth wet with neutral detergent or alcohol. Do not use any organic solvent, such as paint thinner or benzine, strong acid or strong alkali to clean the surface of the E5C4, otherwise the surface of the E5C4 will become damaged.
6
E5C4
E5C4
7
E5C4
E5C4
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H82-E1-1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Systems Components Division 28th Fl., Crystal Tower Bldg. 1-2-27, Shiromi, Chuo-ku, Osaka 540 Japan Phone: 06-949-6012 Fax: 06-949-6021 Printed in Japan 0496-1M (0496) a
8


▲Up To Search▲   

 
Price & Availability of E5C4-Q20J

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X